Smart Thermostat

GridNavigator’s Smart Thermostat is full featured but simple to use, proving accurate control of small commercial HVAC systems. It features a high definition touchscreen and sophisticated energy management software that enables small businesses to take control of their energy costs. The simple programming and intuitive display make it easy for both facility managers and tenants to use. A local override limits user changes, ensuring the greatest energy savings. It is designed to increase comfort during business hours and minimize waste during vacancy hours. Data and remote control are provided by the GridNavigator's mobile app and web portal, allowing users to manage multiple facilities across portfolios remotely.

Communicating Thermostats control 24 Vac commercial single-zone multistage conventional, heat pump and modulating HVAC equipment. Additionally, it allows remote access and the sharing of clock, schedule, set-points, bypass and other system parameters with other devices in a network.

Model #: GN-TS-001

Features Benefit
High-resolution touch-screen Easy to read even from a distance
Intuitive user interface Easy to program and operate
Temporary local override Maximizes energy efficiency by limiting user changes
Wireless communication Easy installation for new buildings or for retrofits
No wires to pull through walls or conduit
Synchronizes operations across multiple HVAC units and portfolios
Automatic connection to GridNavigator’s EMS system
Clock memory Retains settings in the event of power outages lasting as long as two days
General Specifications
Power Requirements 20-30 volts AC; 50/60 Hz
Class 2, 24 volts AC Nominal
2.4 VA not including relay loads
Output Relays Rating 2.5 A continuous/6.0 A surge
<100 ms; 30 volts AC, Class 2
Recommended Wire Size 18 AWG at 100 ft./20AWG at 20 ft.
Ambient Operating Conditions 0˚— 55˚C (32˚— 131˚F) 5%-90% RH non-condensing
Ambient Storage Conditions -40˚to 65˚C (-40˚ to 150˚F) 5%-90% RH non-condensing
Measurement Range 0˚— 117˚F 5%-90% RH
Control Range 41˚— 89˚F
Display Resolution 1˚F / 1% RH
Setpoint Resolution 1˚F
Control Hysteresis 1˚F (actual) / 2˚F (display)
Minimum Deadband 3˚F between heating and cooling (Auto-change)
Minimum Operation Time ON— no minimum
OFF — 3 minutes (Heat and Cool) (fixed)
Clock Retention >48 hours
Communications 2.4 GHz FHSS, 125 mW output (+21 dBm)
Dimensions 5.0” x 6.0” x 1.5”